Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2019, 06:45 AM
  • B 0561_B 0835 _12112019_224931.mp4

Date
12/11/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09109
Time
10:45 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7151
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0561
Downstream MH
B 0835
Dir. of Survey
Downstream
Length Surveyed
35 ft.
Total Length
35 ft.
Structural Index
3
Structural Quick
3600
Structural Rating
18
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole B 0561 to B 0835
MH: B 0561MH: B 0835downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 05612 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start33.1 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish33.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish35 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK35 ft. AMH - Downstream Manhole, Survey Ends - B 0835

Observation photos (2)

  • Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
0MWL
2SCP
35MGOCONNECTION AT MH 9 O'CLOCK
33.1SCP
33.1DAGS
0AMHB 0561
2DAGS
35AMHB 0835

Properties (6)

additional_info
SC378883
custom_field_two
2
customer
LACSD
datetime
2019-12-11T22:45:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false