Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2019, 06:51 AM
  • B 0835_B 0560 _12112019_231339.mp4

Date
12/11/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09108
Time
10:51 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7151
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0835
Downstream MH
B 0560
Dir. of Survey
Downstream
Length Surveyed
107.5 ft.
Total Length
107.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
63
O&M Index
2
O&M Quick
2C00
O&M Rating
42
Overall Index
3
Overall Quick
Overall Rating
105
Pipe schematic from manhole B 0835 to B 0560
MH: B 0835MH: B 0560downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 08350 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start107.5 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish107.5 ft. MSA - Survey Abandoned - DUE TO CORROSION.107.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - DUE TO CORROSION.

    107.5 ft. - Survey Abandoned - DUE TO CORROSION.

Observations (9)

DistanceCodeObservation
2SCP
107.5SCP
2DAGS
0MWM
107.5MSADUE TO CORROSION.
0AMHB 0835
0MGOCONNECTION AT MH 9 O'CLOCK
107.5DAGS
0MWL

Properties (6)

additional_info
SC378883
custom_field_two
5
customer
LACSD
datetime
2019-12-11T22:51:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false