Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2019, 09:54 AM
  • B 0560_B 0559 _12122019_021229.mp4

Date
12/12/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09107
Time
1:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7151
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0559
Downstream MH
B 0560
Dir. of Survey
Upstream
Length Surveyed
417 ft.
Total Length
417 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
249
O&M Index
2
O&M Quick
2P00
O&M Rating
166
Overall Index
3
Overall Quick
Overall Rating
415
Pipe schematic from manhole B 0559 to B 0560
MH: B 0559MH: B 0560upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 05601.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.4 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish415 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start415 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start417 ft. MWM - Water Mark, 20 %of cross sectional area417 ft. MWL - Water Level, 10 %of cross sectional area417 ft. AMH - Upstream Manhole, Survey Begins - B 0560

Observation photos (2)

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2SCP
415.6DAGS
0MWM
0MWL
417AMHB 0560
0AMHB 0560
2DAGS
415.6SCP

Properties (6)

additional_info
SC378883
custom_field_two
2
customer
LACSD
datetime
2019-12-12T01:54:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false