Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2019, 09:12 PM
  • 08 0474_08 0596 _12022019_132356.mp4

Date
12/02/2019
W/O
792793
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00025
PipeID
P00531
Time
1:12 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6830
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792793_TV08101_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0596
Downstream MH
08 0474
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
13
Pipe schematic from manhole 08 0596 to 08 0474
MH: 08 0596MH: 08 0474upstream0 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MGO - General Observation - MAG COAT THROUGHOUT0 ft. MSA - Survey Abandoned - UNABLE TO GO U/S0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. MWM - Water Mark, 75 %of cross sectional area2 ft. MWL - Water Level, 50 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - 08 05962 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • Survey Abandoned - UNABLE TO GO U/S

    2 ft. - Survey Abandoned - UNABLE TO GO U/S

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
2SRC
0MWM
0MWL
2MGOMAG COAT THROUGHOUT
2MSAUNABLE TO GO U/S
2SAP
0AMH08 0596
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2019-12-02T13:12:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false