Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 26, 2019, 06:18 AM
  • 08 0476_08 0475 _11252019_224611.mp4

Date
11/25/2019
W/O
792793
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00025
PipeID
P00533
Time
10:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6341
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792793_TV08101_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0476
Downstream MH
08 0475
Dir. of Survey
Downstream
Length Surveyed
730.6 ft.
Total Length
730.6 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 08 0476 to 08 0475
MH: 08 0476MH: 08 0475downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04762 ft. MGO - General Observation - MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28 ft. SRC - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: YES42.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start727.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish730.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish730.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0475730.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: YES

    28 ft. - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    42.5 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
2MGOMAG COAT
727.8SRC
28SRC
2SAP
0MWM
730.6AMH08 0475
730.2SAP
42.5SRC
730.6SSS
2SSS
0AMH08 0476

Properties (6)

additional_info
SC365785
custom_field_two
2
customer
LACSD
datetime
2019-11-25T22:18:26-08:00
documentation
PROPIPE
is_lateral_inspection
false