Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2019, 08:04 PM
  • 08 0596_D 0008 _12022019_123302.mp4

Date
12/02/2019
W/O
792793
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00025
PipeID
P00530
Time
12:04 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6830
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792793_TV08101_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0596
Downstream MH
D 0008
Dir. of Survey
Downstream
Length Surveyed
683 ft.
Total Length
683 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 08 0596 to D 0008
MH: 08 0596MH: D 0008downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05960 ft. MWM - Water Mark, 75 %of cross sectional area2 ft. MGO - General Observation - MAG COAT THROUGHOUT2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start65.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start683 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish683 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish683 ft. AMH - Downstream Manhole, Survey Ends - D 0008683 ft. MGO - General Observation - ENDING VIDEO PARACHUTE IN OTHER LINE683 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    65.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
683SAP
2MGOMAG COAT THROUGHOUT
0MWL
0AMH08 0596
0MWM
683SRC
2SRC
65.8SSS
2SAP
683AMHD 0008
683MGOENDING VIDEO PARACHUTE IN OTHER LINE
683SSS

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-12-02T12:04:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false