Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2019, 06:56 AM
  • 02 0111_02 0110 _12042019_231613.mp4

Date
12/04/2019
W/O
798354
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00237
PipeID
P02278
Time
10:56 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7141
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798354_TV02350_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0110
Downstream MH
02 0111
Dir. of Survey
Upstream
Length Surveyed
315.2 ft.
Total Length
315.2 ft.
Structural Index
3
Structural Quick
423K
Structural Rating
313
O&M Index
2
O&M Quick
412M
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
457
Pipe schematic from manhole 02 0110 to 02 0111
MH: 02 0110MH: 02 0111upstream0 ft. MGO - General Observation - COCKROACHES AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 02 01111.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN78.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 25% GREASE-LATERAL/OPEN78.8 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: NO84.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN104 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES105 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - CONN BROKEN/55% GREASE-LATERAL/OPEN128.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 65% GREASE-LATERAL/OPEN155.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 35% GREASE-LATERAL/OPEN176.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 45% GREASE-LATERAL/OPEN206.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - CONN BROKEN/OPEN230 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN232.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 40% GREASE-LATERAL/OPEN253 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 45% GREASE-LATERAL/OPEN282.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start308.9 ft. JSM - Joint Separated Medium313.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start313.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start315.2 ft. AMH - Downstream Manhole, Survey Begins - 02 0110315.2 ft. MWM - Water Mark, 35 %of cross sectional area315.2 ft. MWL - Water Level, 30 %of cross sectional area315.2 ft. MGO - General Observation - COCKROACHES AT MH

Observation photos (7)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Joint Separated Medium

    6.3 ft. - Joint Separated Medium

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    211.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: NO

    236.4 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES AT MH

    315.2 ft. - General Observation - COCKROACHES AT MH

Observations (27)

DistanceCodeObservation
159.5TFD35% GREASE-LATERAL/OPEN
12.1CM
315.2MGOCOCKROACHES AT MH
62.2TFD45% GREASE-LATERAL/OPEN
0AMH02 0110
82.5TFD40% GREASE-LATERAL/OPEN
260.8TFOPEN
32.5TFC
0MWM
186.6TFD65% GREASE-LATERAL/OPEN
315.2AMH02 0111
6.3JSM
210.2TFDCONN BROKEN/55% GREASE-LATERAL/OPEN
2SSS
0MWL
231TFOPEN
313.3DAGS
138.9TFD45% GREASE-LATERAL/OPEN
236.9TFD25% GREASE-LATERAL/OPEN
236.4FM
313.3CM
313SSS
2DAGS
109TFDCONN BROKEN/OPEN
85.2TFOPEN
211.2FM
0MGOCOCKROACHES AT MH

Properties (6)

additional_info
SC378873
custom_field_two
2
customer
LACSD
datetime
2019-12-04T22:56:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false