Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2019, 07:46 AM
  • 02 0108_02 0107 _12052019_001206.mp4

Date
12/04/2019
W/O
798354
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00237
PipeID
P02275
Time
11:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7141
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_798354_TV02350_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0108
Downstream MH
02 0107
Dir. of Survey
Downstream
Length Surveyed
368.1 ft.
Total Length
368.1 ft.
Structural Index
3
Structural Quick
534A
Structural Rating
424
O&M Index
2
O&M Quick
413D
O&M Rating
234
Overall Index
2
Overall Quick
Overall Rating
658
Pipe schematic from manhole 02 0108 to 02 0107
MH: 02 0108MH: 02 0107downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01080 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH0 ft. MGO - General Observation - CONN @ MH 6 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.5 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES20.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN25.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES46.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish59.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 25% GREASE-LATERAL86.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN110.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN193.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS228.1 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start228.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start232 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish232 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish236 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN237.6 ft. FM - Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES238.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN250.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN277.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN323.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish323.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN350.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"353 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN365.6 ft. MGO - General Observation - COCKROACHES AT MH365.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish365.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish366 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish368 ft. MGO - General Observation - SHELVES CHIPPED @ MH 9 TO 3 O'CLOCK368 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH368.1 ft. MGO - General Observation - DROP CONN @ MH 9 O'CLOCK/ACTIVE368.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0107

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, at 04 o'clock,  , within 8 inches of joint: YES

    25.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    228.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

    237.6 ft. - Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES AT MH

    365.6 ft. - General Observation - COCKROACHES AT MH

Observations (41)

DistanceCodeObservation
0AMH02 0108
236TFOPEN
368MGOSHELVES CHIPPED @ MH 9 TO 3 O'CLOCK
323.3DSZ
2CM
2SSS
193.7DSZDEBRIS
366SSS
0VC@ MH
353TFOPEN
323.3TFOPEN
121.9TFA
350.2TFC
25.5DAGS
250.6TFOPEN
0MGOCONN @ MH 6 O'CLOCK/ACTIVE
232FM
110.3TFA
368.1MGODROP CONN @ MH 9 O'CLOCK/ACTIVE
4.1FM
365.6MGOCOCKROACHES AT MH
0MWL
365.6CM
175.7TFOPEN
237.6FM
238.8TFOPEN
172.9TFC
2DAGS
86.4TFOPEN
59.5TFD25% GREASE-LATERAL
228.1B
368VC@ MH
46.3FM
0MWM
20.5TFOPEN
365.6DAGS
6.5B
368.1AMH02 0107
228.7FM
277.6TFOPEN
232B

Properties (6)

additional_info
SC378873
custom_field_two
2
customer
LACSD
datetime
2019-12-04T23:46:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false