Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2019, 10:18 AM
  • 02 1362_02 1361 _11252019_023640.mp4

Date
11/25/2019
W/O
798190
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00277
PipeID
P03885
Time
2:18 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6829
Sewer Name
02 JANE STREET BRANCH TRUNK
City
E LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
RFIR_WO_798190_TV02342_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1362
Downstream MH
02 1361
Dir. of Survey
Downstream
Length Surveyed
272.6 ft.
Total Length
272.6 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole 02 1362 to 02 1361
MH: 02 1362MH: 02 1361downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13620 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"7.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES10.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start48.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"111.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"112.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES135.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"190.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"232.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"268.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"269.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish269.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish272.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1361

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    112.6 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
2.2DAGS
5.7TF
190.5TF
232.4TF
0AMH02 1362
111.6TF
272.6AMH02 1361
7.3CM
268.5TFA
135.7TF
10.4CM
48.1TF
269.3DAGS
269.3CM
0MWL
112.6DAE
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-11-25T02:18:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false