Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2019, 09:25 AM
  • 02 1351_02 1350_12022019_013917.mp4

Date
12/02/2019
W/O
798190
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00277
PipeID
P03874
Time
1:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7136
Sewer Name
02 JANE STREET BRANCH TRUNK
City
COMMERCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_798190_TV02342_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 1351
Downstream MH
02 1350
Dir. of Survey
Downstream
Length Surveyed
376.2 ft.
Total Length
376.2 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
204
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
354
Pipe schematic from manhole 02 1351 to 02 1350
MH: 02 1351MH: 02 1350downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13510 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start32.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start151.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"371.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish376.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1350, ABANDONED MH.

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - 02 1350, ABANDONED MH.

    376.2 ft. - Downstream Manhole, Survey Ends - 02 1350, ABANDONED MH.

Observations (10)

DistanceCodeObservation
151.2TFA
371.3CM
0AMH02 1351
376.2DAGS
376.2AMH02 1350, ABANDONED MH.
0MWM
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
32.3CM

Properties (6)

additional_info
SC378868
custom_field_two
3
customer
LACSD
datetime
2019-12-02T01:25:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false