Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2019, 11:33 AM
  • 02 0164_02 0163 _12032019_035039.mp4

Date
12/03/2019
W/O
798191
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02467
Time
3:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7139
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798191_TV02327_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 0164
Downstream MH
02 0163
Dir. of Survey
Downstream
Length Surveyed
333.5 ft.
Total Length
333.5 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0164 to 02 0163
MH: 02 0164MH: 02 0163downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01642 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start25.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start57.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish77 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start104.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"107.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"146.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish159 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"161.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"177.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"216.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start220.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"247.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS325.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish330.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0163

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    25.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    77 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    220.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MWM
333.5AMH02 0163
216.7TFA
177.3TFC
220.3CL
161.9TFC
104.1TFA
0MWL
325.5CL
267.6DSZDEBRIS
146.7CL
25.5CL
0AMH02 0164
107.3TFA
247.7TFC
2DAGS
77CL
330.9DAGS
220.3TFA
57.9CL
159TFC

Properties (6)

additional_info
SC378871
custom_field_two
3
customer
LACSD
datetime
2019-12-03T03:33:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false