Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 10:35 AM
  • J 0032A_J 0032 _12112019_024610.mp4

Date
12/11/2019
W/O
798298
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00061
PipeID
P11609
Time
2:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7208
Sewer Name
J JOINT OUTFALL J - UNIT 2B
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798298_TV05231_NOV2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
J 0032A
Downstream MH
J 0032
Dir. of Survey
Downstream
Length Surveyed
7.1 ft.
Total Length
7.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
13
Pipe schematic from manhole J 0032A to J 0032
MH: J 0032AMH: J 0032downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 0032A0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES7.1 ft. OBZ - Obstacles Other, 50 %of cross sectional area, from 09 to 03 o'clock - REINFORCEMENT HANGING OFF7.1 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observation photos (4)

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Obstacles Other, 50 %of cross sectional area, from 09 to 03 o'clock - REINFORCEMENT HANGING OFF

    7.1 ft. - Obstacles Other, 50 %of cross sectional area, from 09 to 03 o'clock - REINFORCEMENT HANGING OFF

  • Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

    7.1 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observations (7)

DistanceCodeObservation
0MWM
0AMHJ 0032A
0MWL
2.1SRC
7.1OBZREINFORCEMENT HANGING OFF
7.1MSAVIEW OF D/S SIPHON FROM U/S MH
2.1SAP

Properties (7)

additional_info
SC398502
custom_field_two
1
customer
LACSD
datetime
2019-12-11T02:35:00-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
36539