Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2019, 06:34 PM
  • 15 1044_15 0060_12132019_105144.mp4

Date
12/13/2019
W/O
798599
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11955
Time
10:34 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6833
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_798599_TV15206_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 1044
Downstream MH
15 0060
Dir. of Survey
Downstream
Length Surveyed
147.5 ft.
Total Length
147.5 ft.
Structural Index
3
Structural Quick
4411
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 15 1044 to 15 0060
MH: 15 1044MH: 15 0060downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 104464.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES72.7 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES104.9 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES111 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES145.6 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES147.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0060

Observation photos (5)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    64.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    72.7 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

    104.9 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    111 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

    145.6 ft. - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
104.9B
0MWL
0MWM
72.7FM
64.1FM
147.5AMH15 0060
145.6CC
0AMH15 1044
111FM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-12-13T10:34:39-08:00
documentation
PRO PIPE
is_lateral_inspection
false