Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2019, 03:44 PM
  • 15 0059_15 0058_12132019_081006.mp4

Date
12/13/2019
W/O
798599
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11952
Time
7:44 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6833
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_798599_TV15206_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0059
Downstream MH
15 0058
Dir. of Survey
Downstream
Length Surveyed
155.2 ft.
Total Length
155.2 ft.
Structural Index
3
Structural Quick
413B
Structural Rating
45
O&M Index
2
O&M Quick
3225
O&M Rating
17
Overall Index
3
Overall Quick
Overall Rating
62
Pipe schematic from manhole 15 0059 to 15 0058
MH: 15 0059MH: 15 0058downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 00590 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area8.9 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES10 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"11.3 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES21.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"46.6 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR46.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES51.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"77.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"95.2 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start103.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"127.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"129 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start153.1 ft. RMC - Roots Medium Connection, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YES154.7 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish154.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish154.8 ft. RML - Roots Medium Lateral, from 03 to 06 o'clock, 15 %, within 8 inches of joint: YES154.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"155.2 ft. MSA - Survey Abandoned - UNABLE TO GET PAST

Observation photos (9)

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    8.9 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    11.3 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR

    46.6 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    46.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    95.2 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    129 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YES

    153.1 ft. - Roots Medium Connection, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Medium Lateral, from 03 to 06 o'clock, 15 %, within 8 inches of joint: YES

    154.8 ft. - Roots Medium Lateral, from 03 to 06 o'clock, 15 %, within 8 inches of joint: YES

  • Survey Abandoned - UNABLE TO GET PAST

    155.2 ft. - Survey Abandoned - UNABLE TO GET PAST

Observations (21)

DistanceCodeObservation
21.9TFC
46.9CM
10TFC
46.6RFJ
154.8RML
154.7CM
153.1RMC
0AMH15 0059
0MWL
77.6TFC
8.9CS
103.6TFC
154.8TF
11.3FM
154.7DAE
127.7TFC
129DAE
0MWM
155.2MSAUNABLE TO GET PAST
51.2TFC
95.2CM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-12-13T07:44:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false