Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 06:41 PM
  • 15 0056_15 0055 _12112019_111107.mp4

Date
12/11/2019
W/O
798599
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11949
Time
10:41 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6832
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_798599_TV15206_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0056
Downstream MH
15 0055
Dir. of Survey
Downstream
Length Surveyed
284.3 ft.
Total Length
284.3 ft.
Structural Index
3
Structural Quick
423D
Structural Rating
93
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
205
Pipe schematic from manhole 15 0056 to 15 0055
MH: 15 0056MH: 15 0055downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00560 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.5 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES14.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"35.1 ft. CS - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES39.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"65.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"89.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"116.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"127.2 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES135.6 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES139.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"141.6 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES150.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start166.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"190.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"217.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"241.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"267.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"281.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish281.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0055284.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (7)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    7.5 ft. - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

    35.1 ft. - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    127.2 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    135.6 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    141.6 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    150.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
2DAGS
65.7TF
150.6CM
89.8TFC
267.9TFC
7.5FM
14.9TFC
127.2CM
166.6TFA
284.3AMH15 0055
135.6CS
141.6FM
281.3DAGS
116.4TFC
241.3TFC
139.5TFC
35.1CS
39.3TFC
190.9TF
0MWM
284.3MGOCONNECTION AT MH 9 O'CLOCK
281.3CM
217.5TFC
0MWL
0AMH15 0056
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-12-11T10:41:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false