Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 07:12 PM
  • 15 0055_15 0054 _12112019_112453.mp4

Date
12/11/2019
W/O
798599
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11948
Time
11:12 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6832
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_798599_TV15206_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0055
Downstream MH
15 0054
Dir. of Survey
Downstream
Length Surveyed
94.2 ft.
Total Length
94.2 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
43
Pipe schematic from manhole 15 0055 to 15 0054
MH: 15 0055MH: 15 0054downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00552.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.5 ft. CS - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES7.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"23.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES33.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"58.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"81.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"83.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES91.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish94.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0054

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

    3.5 ft. - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    23.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    83.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
91.3DAGS
33.8TFC
3.5CS
23.8CL
58.1TF
0MGOCONNECTION AT MH 9 O'CLOCK
94.2AMH15 0054
7.4TFC
81.7TFA
2.2DAGS
83.1CM
0MWM
0MWL
0AMH15 0055

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-12-11T11:12:13-08:00
documentation
PRO PIPE
is_lateral_inspection
false