Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 07:30 PM
  • 15 0054_15 0053 _12112019_115605.mp4

Date
12/11/2019
W/O
798599
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11947
Time
11:30 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6832
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_798599_TV15206_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0054
Downstream MH
15 0053
Dir. of Survey
Downstream
Length Surveyed
242 ft.
Total Length
242 ft.
Structural Index
3
Structural Quick
4137
Structural Rating
25
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
121
Pipe schematic from manhole 15 0054 to 15 0053
MH: 15 0054MH: 15 0053downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00542 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13.1 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES14.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"38.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"64.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"88.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"112.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6"135.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES139.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"146.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES165.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"189.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"205.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES212.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES216.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"224.5 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES235.4 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES238.1 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES240 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"240 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish242 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK242 ft. AMH - Downstream Manhole, Survey Ends - 15 0053

Observation photos (9)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    13.1 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    135.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    146.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    205.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    212.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    224.5 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    235.4 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    238.1 ft. - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
88.7TFC
139.1TFC
38.7TFC
189.5TFC
13.1CM
240TFC
135.5CM
242MGOCONNECTION AT MH 9 O'CLOCK
242AMH15 0053
165.2TFC
0MWM
212.1CM
0MWL
2DAGS
14.2TFC
216.4TFC
240DAGS
205.8CM
224.5CM
0AMH15 0054
238.1FS
146.2CM
64.9TFC
112.9TFC
235.4FM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-12-11T11:30:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false