- Date
- 12/16/2019
- W/O
- 798599
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00622
- PipeID
- P11911
- Time
- 3:43 AM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7187
- Sewer Name
- 15 PUENTE TRUNK
- City
- BASSETT
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 34
- Purpose
- Routine Assessment
- Project
- RFIR_WO_798599_TV15206_NOV2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 15 0022
- Downstream MH
- 15 0021
- Dir. of Survey
- Downstream
- Length Surveyed
- 469.1 ft.
- Total Length
- 469.1 ft.
- Structural Index
- 3
- Structural Quick
- 4231
- Structural Rating
- 13
- O&M Index
- 2
- O&M Quick
- 2800
- O&M Rating
- 16
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 29
Pipe schematic from manhole 15 0022 to 15 0021 Observation photos (5)

2.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

37.2 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

42.5 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

195.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

274.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start