Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2019, 09:38 AM
  • H 0609_H 0608 _12172019_013727.mp4

Date
12/17/2019
W/O
798664
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00190
PipeID
P11030
Time
1:38 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7154
Sewer Name
H JOINT OUTFALL H - UNIT 8G
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_798664_TV15233_NOV2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0609
Downstream MH
H 0608
Dir. of Survey
Downstream
Length Surveyed
821.1 ft.
Total Length
821.1 ft.
Structural Index
3
Structural Quick
3`2`
Structural Rating
815
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
815
Pipe schematic from manhole H 0609 to H 0608
MH: H 0609MH: H 0608downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06090 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start42.9 ft. MGO - General Observation - MAG COATING THROUGHOUT45.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"219 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"339.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"412.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"457.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"561.4 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"578.4 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"818.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish818.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish821.1 ft. AMH - Downstream Manhole, Survey Ends - H 0608

Observation photos (2)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
2SSS
561.4TBA
412.5TBA
45.7TBA
0AMHH 0609
42.9MGOMAG COATING THROUGHOUT
457.9TBA
339.8TBA
219TBA
2SAP
578.4TBA
818.8SSS
0MWL
98.9TBA
0MWM
198.7TBA
821.1AMHH 0608
818.8SAP

Properties (7)

additional_info
SC378886
custom_field_two
3
customer
LACSD
datetime
2019-12-17T01:38:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27198