Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2019, 08:49 AM
  • 18 0669_18 0668 _12042019_010802.mp4

Date
12/04/2019
W/O
798156
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14518
Time
12:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7140
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798156_TV18081_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
353 ft.
Total Length
353 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06690 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES42.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"48.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start84.4 ft. CM - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES96.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish150.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start198.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"204.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.2 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES301.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"351.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353 ft. AMH - Downstream Manhole, Survey Ends - 18 0668

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    23.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    48.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

    84.4 ft. - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: YES

    212.2 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
42.5TBA
48.9CL
351.3CM
101.7TFA
198.4TFC
96.4TFA
204.1TFC
0MWL
0AMH18 0669
351.3DAGS
353AMH18 0668
0MWM
150.9CL
84.4CM
2DAGS
212.2H
150.9CM
301.9TFC
307.1TFC
23.7CL

Properties (5)

additional_info
SC378872
customer
LACSD
datetime
2019-12-04T00:49:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false