Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 10:54 AM
  • 18 0657_18 0656 _12112019_032317.mp4

Date
12/11/2019
W/O
798156
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14506
Time
2:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7150
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798156_TV18081_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0656
Downstream MH
18 0657
Dir. of Survey
Upstream
Length Surveyed
327.3 ft.
Total Length
327.3 ft.
Structural Index
2
Structural Quick
4229
Structural Rating
26
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
158
Pipe schematic from manhole 18 0656 to 18 0657
MH: 18 0656MH: 18 0657upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 06572.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish7.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"12.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"25.2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES105 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES146.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish156.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start159.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish166 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start206.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"206.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES206.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES211.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"265.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES270.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES306.9 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 06 to 12 o'clock, , within 8 inches of joint: YES322.3 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES325.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start327.3 ft. MWM - Water Mark, 25 %of cross sectional area327.3 ft. MWL - Water Level, 5 %of cross sectional area327.3 ft. AMH - Downstream Manhole, Survey Begins - 18 0656

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    5 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Other, 5 %of cross sectional area, from 06 to 12 o'clock,  , within 8 inches of joint: YES

    20.4 ft. - Deposits Attached Other, 5 %of cross sectional area, from 06 to 12 o'clock, , within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    56.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    61.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    120.9 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    120.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

    161.3 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    170.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    212 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    302.1 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
167.5CL
327.3AMH18 0657
5FM
120.9TBA
319.6TFA
20.4DAZ
120.9TFC
161.3CL
56.9CL
0MWM
212CL
120.9CL
170.8CL
61.5CL
120.9CL
180.7CL
325.1DAGS
302.1FM
222.3TFC
0MWL
0AMH18 0656
216.6TFC
115.6TFC
314.8TFA
2DAGS

Properties (6)

additional_info
SC378882
custom_field_two
1
customer
LACSD
datetime
2019-12-11T02:54:37-08:00
documentation
PRO PIPE
is_lateral_inspection
false