Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2019, 11:13 AM
  • 05 2162_05 2161 _12052019_032025.mp4

Date
12/05/2019
W/O
798187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00509
PipeID
P07304
Time
3:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6353
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_798187_TV05190_NOV2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
05 2162
Downstream MH
05 2161
Dir. of Survey
Downstream
Length Surveyed
19 ft.
Total Length
19 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 2162 to 05 2161
MH: 05 2162MH: 05 2161downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 21620.1 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES4.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES19 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    4.6 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

    19 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observations (6)

DistanceCodeObservation
2.1SAP
0.1MWM
0MWL
4.6SRV
0AMH05 2162
19MSAVIEW OF D/S SIPHON FROM U/S MH

Properties (7)

additional_info
SC365796
custom_field_two
2
customer
LACSD
datetime
2019-12-05T03:13:16-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26616