Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2019, 06:08 AM
  • 03 0413_03 0412 _11212019_224002.mp4

Date
11/21/2019
W/O
798173
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00373
PipeID
P05175
Time
10:08 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7173
Sewer Name
03 MARINA TRUNK, SECTION 4
City
LONG BEACH
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_798173_TV03163_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
03 0413
Downstream MH
03 0412
Dir. of Survey
Downstream
Length Surveyed
303.9 ft.
Total Length
303.9 ft.
Structural Index
3
Structural Quick
4232
Structural Rating
16
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 03 0413 to 03 0412
MH: 03 0413MH: 03 0412downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 04132.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES13 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES130.5 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES152.1 ft. TBC - Tap Break-In Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"156.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"206.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start206.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish303.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED303.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0412

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    7.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    115.5 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    130.5 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    206.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
303.9MGOCONNECTION AT MH 9 O'CLOCK CAPPED
152.1TBC
301.3FM
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
130.5FM
301.3DAGS
115.5FL
0MWM
0AMH03 0413
206.1FM
2.4DAGS
156.5TB
206.1CM
13CM
303.9AMH03 0412
7.9CL

Properties (6)

additional_info
SC398413
custom_field_two
1
customer
LACSD
datetime
2019-11-21T22:08:13-08:00
documentation
PROPIPE
is_lateral_inspection