Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2019, 06:49 AM
  • 02 1449_02 1448 _11212019_231706.mp4

Date
11/21/2019
W/O
798208
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00307
PipeID
P04689
Time
10:49 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7134
Sewer Name
02 TRACT #5445 TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_798208_TV02303_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1449
Downstream MH
02 1448
Dir. of Survey
Downstream
Length Surveyed
240.2 ft.
Total Length
240.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
2
O&M Quick
412H
O&M Rating
98
Overall Index
3
Overall Quick
Overall Rating
236
Pipe schematic from manhole 02 1449 to 02 1448
MH: 02 1449MH: 02 1448downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14492 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start85.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"183 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.9 ft. MMC - Material Change, Concrete pipe (non-reinfored)229.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish229.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start238.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish238.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish239 ft. MGO - General Observation - VERMIN (RAT) @ D/S MH - 9 O'CLOCK240.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1448240.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Concrete pipe (non-reinfored)

    229.9 ft. - Material Change, Concrete pipe (non-reinfored)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    229.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    240.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
240.2AMH02 1448
88.5TF
229.9MMC
229.9CM
238.9DAGS
183TF
0MWL
0MGOCOCKROACHES IN MANHOLE
136.8TFA
134.6TF
8.1CM
0MWM
229.9SAP
2DAGS
0AMH02 1449
85.8TFC
239MGOVERMIN (RAT) @ D/S MH - 9 O'CLOCK
240.2MGOCOCKROACHES IN MANHOLE
185.7TF
238.9SAP

Properties (6)

additional_info
SC378866
custom_field_two
3
customer
LACSD
datetime
2019-11-21T22:49:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false