Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2019, 10:54 AM
  • 05 0353_05 0352 _11252019_030624.mp4

Date
11/25/2019
W/O
798186
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05567
Time
2:54 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6341
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_798186_TV05325_NOV2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0353
Downstream MH
05 0352
Dir. of Survey
Downstream
Length Surveyed
428.9 ft.
Total Length
428.9 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
425
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
425
Pipe schematic from manhole 05 0353 to 05 0352
MH: 05 0353MH: 05 0352downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03530 ft. MGO - General Observation - CONN @ 3 O'CLOCK2 ft. SZ - Surface Other, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - 70% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start426 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish427 ft. SZ - Surface Other, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 70% MAG428.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish428.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0352

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2.5SAP
0MWL
427SZ70% MAG
428.9SAP
0MWM
426SSS
428.9AMH05 0352
0AMH05 0353
2SZ70% MAG
0MGOCONN @ 3 O'CLOCK
2SSS

Properties (6)

additional_info
SC365784
custom_field_two
3
customer
LACSD
datetime
2019-11-25T02:54:21-08:00
documentation
PROPIPE
is_lateral_inspection
false