Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2019, 10:17 AM
  • E 0044_E 0043_11212019_022922.mp4

Date
11/21/2019
W/O
792653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00028
PipeID
P11271
Time
2:17 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7172
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_792653_TV01124_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0043
Downstream MH
E 0044
Dir. of Survey
Upstream
Length Surveyed
215.3 ft.
Total Length
215.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole E 0043 to E 0044
MH: E 0043MH: E 0044upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETED-@ OBTRUCTION (UNKNOWN @ 5 TO 7 O'CLOCK)0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish207.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start211.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start215.3 ft. AMH - Downstream Manhole, Survey Begins - E 0043215.3 ft. MWM - Water Mark, 20 %of cross sectional area215.3 ft. MWL - Water Level, 10 %of cross sectional area215.3 ft. MGO - Reversal Inspection

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHE 0043
215.3MSAREVERSAL COMPLETED-@ OBTRUCTION (UNKNOWN @ 5 TO 7 O'CLOCK)
0MWM
0MWL
0MGO
3.4SAP
7.9SSS
215.3SSS
215.3SAP

Properties (6)

additional_info
SC398412
custom_field_two
3
customer
LACSD
datetime
2019-11-21T02:17:45-08:00
documentation
PROPIPE
is_lateral_inspection
false