Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2019, 06:53 AM
  • E 0058_E 0057_11122019_231904.mp4

Date
11/12/2019
W/O
792653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00028
PipeID
P11288
Time
10:53 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7160
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792653_TV01124_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
E 0058
Downstream MH
E 0057
Dir. of Survey
Downstream
Length Surveyed
679.7 ft.
Total Length
679.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole E 0058 to E 0057
MH: E 0058MH: E 0057downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00580.1 ft. MWM - Water Mark, 40 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start120.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8"294.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE CONNECTION678.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish678.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish679.7 ft. AMH - Downstream Manhole, Survey Ends - E 0057

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.6SAP
0MWL
0AMHE 0058
0.1MWM
294.5TBACTIVE CONNECTION
2.6SSS
678.4SSS
120.4TB
679.7AMHE 0057
678.4SAP

Properties (6)

additional_info
SC378695
custom_field_two
3
customer
LACSD
datetime
2019-11-12T22:53:11-08:00
documentation
PROPIPE
is_lateral_inspection
false