Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2019, 09:03 AM
  • E 0056_E 0055_11132019_012107.mp4

Date
11/13/2019
W/O
792653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00028
PipeID
P11285
Time
1:03 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7160
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792653_TV01124_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
E 0056
Downstream MH
E 0055
Dir. of Survey
Downstream
Length Surveyed
612.8 ft.
Total Length
612.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole E 0056 to E 0055
MH: E 0056MH: E 0055downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00560.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0.3 ft. MWM - Water Mark, 45 %of cross sectional area2.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start609.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish609.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish612.8 ft. AMH - Downstream Manhole, Survey Ends - E 0055612.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
612.8AMHE 0055
0.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
609.7SSS
0.3MWM
2.9SSS
0MWL
609.7SAP
2.8SAP
612.8MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMHE 0056

Properties (6)

additional_info
SC378695
custom_field_two
3
customer
LACSD
datetime
2019-11-13T01:03:14-08:00
documentation
PROPIPE
is_lateral_inspection
false