Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 10:14 AM
  • E 0047A_E 0047_11142019_022348.mp4

Date
11/14/2019
W/O
792653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00028
PipeID
P11275
Time
2:14 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7161
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_792653_TV01124_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0047A
Downstream MH
E 0047
Dir. of Survey
Downstream
Length Surveyed
142.8 ft.
Total Length
142.8 ft.
Structural Index
3
Structural Quick
513E
Structural Rating
143
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
143
Pipe schematic from manhole E 0047A to E 0047
MH: E 0047AMH: E 0047downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK STOP LOG0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 0047A0 ft. MWM - Water Mark, 35 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SRVM - Surface Reinforcement Visible Mechanical, at 02 o'clock, within 8 inches of joint: NO4.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start141.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish141.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish142.8 ft. AMH - Downstream Manhole, Survey Ends - E 0047

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
141.3SAP
0MGOCONNECTION AT MH 9 O'CLOCK STOP LOG
141.3SSS
0MWL
0AMHE 0047A
2.6SAP
4.7SSS
142.8AMHE 0047
3SRVM
0MWM

Properties (6)

additional_info
SC378696
custom_field_two
3
customer
LACSD
datetime
2019-11-14T02:14:09-08:00
documentation
PROPIPE
is_lateral_inspection
false