Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2019, 11:00 AM
  • E 0039_E 0038_11152019_031854.mp4

Date
11/15/2019
W/O
792653
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00028
PipeID
P11266
Time
3:00 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7162
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_792653_TV01124_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0039
Downstream MH
E 0038
Dir. of Survey
Downstream
Length Surveyed
500.6 ft.
Total Length
500.6 ft.
Structural Index
3
Structural Quick
3S2R
Structural Rating
485
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
485
Pipe schematic from manhole E 0039 to E 0038
MH: E 0039MH: E 0038downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 00390 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - COCKROACHES THROUGHOUT SECTION - 7 TO 5 O'CLOCK3.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start251 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE CONNECTION498.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish498.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish500.6 ft. AMH - Downstream Manhole, Survey Ends - E 0038

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
498.1SAV
29.2SSS
500.6AMHE 0038
3.9SAV
0AMHE 0039
498.1SSS
2MGOCOCKROACHES THROUGHOUT SECTION - 7 TO 5 O'CLOCK
0MWL
251TBACTIVE CONNECTION
0MWM

Properties (6)

additional_info
SC398402
custom_field_two
3
customer
LACSD
datetime
2019-11-15T03:00:14-08:00
documentation
PROP
is_lateral_inspection
false