Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2019, 11:11 AM
  • 29 0448_29 0447 _11122019_032413.mp4

Date
11/12/2019
W/O
792790
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01090
PipeID
P24488
Time
3:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6331
Sewer Name
29 ALAMITOS PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_792790_TV29104_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0448
Downstream MH
29 0447
Dir. of Survey
Downstream
Length Surveyed
202.4 ft.
Total Length
202.4 ft.
Structural Index
3
Structural Quick
413G
Structural Rating
121
O&M Index
1
O&M Quick
4131
O&M Rating
20
Overall Index
3
Overall Quick
Overall Rating
141
Pipe schematic from manhole 29 0448 to 29 0447
MH: 29 0448MH: 29 0447downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 04480 ft. MWM - Water Mark, 10 %of cross sectional area5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"10 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"47.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.9 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES47.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES49.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start94.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.5 ft. RBL - Roots Ball Lateral, at 10 o'clock, 85 %97.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish145 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.5 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock189.5 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1"202.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.4 ft. AMH - Downstream Manhole, Survey Ends - 29 0447

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    47.9 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Roots Ball Lateral, at 10 o'clock, 85 %

    94.5 ft. - Roots Ball Lateral, at 10 o'clock, 85 %

  • Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    189.5 ft. - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

Observations (22)

DistanceCodeObservation
47.9FM
80.1RFJ
0MWL
5.8CM
189.5RFC
44.2TF
202.4CM
10TFC
94.5TF
97.1TF
47.9RFJ
0AMH29 0448
47.2TFC
202.4AMH29 0447
0MWM
147.4TF
49.5TF
189.5TFI
7.1TFC
135.9RFJ
94.5RBL
145TFA

Properties (6)

additional_info
SC365774
custom_field_two
3
customer
LACSD
datetime
2019-11-12T03:11:32-08:00
documentation
PROPIPE
is_lateral_inspection
false