Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2019, 09:19 AM
  • C 0568_C 0567_11242019_180152.mp4

Date
11/22/2019
W/O
798188
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00362
PipeID
P04752
Time
1:19 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7174
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_798188_TV03084_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
C 0568
Downstream MH
C 0567
Dir. of Survey
Downstream
Length Surveyed
329.1 ft.
Total Length
329.1 ft.
Structural Index
2
Structural Quick
3L2W
Structural Rating
442
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
442
Pipe schematic from manhole C 0568 to C 0567
MH: C 0568MH: C 0567downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05680 ft. MWM - Water Mark, 45 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.4 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES27.8 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start114.6 ft. FS - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES199.5 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish215.7 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start327 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish329.1 ft. AMH - Downstream Manhole, Survey Ends - C 0567

Observation photos (4)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    24.4 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    27.8 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    114.6 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    215.7 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
27.8CS
215.7CS
327SSS
329.1AMHC 0567
24.4CL
199.5CS
0MWL
2CM
0AMHC 0568
2SSS
114.6FS
327CM
0MWM
327CS

Properties (6)

additional_info
SC398414
custom_field_two
3
customer
LACSD
datetime
2019-11-22T01:19:14-08:00
documentation
PROPIPE
is_lateral_inspection
false