Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2019, 09:03 AM
  • C 0563_C 0562_11212019_012627.mp4

Date
11/21/2019
W/O
798188
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00362
PipeID
P04747
Time
1:03 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7171
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_798188_TV03084_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
C 0563
Downstream MH
C 0562
Dir. of Survey
Downstream
Length Surveyed
459.9 ft.
Total Length
459.9 ft.
Structural Index
3
Structural Quick
413c
Structural Rating
922
O&M Index
2
O&M Quick
2c00
O&M Rating
360
Overall Index
2
Overall Quick
Overall Rating
1282
Pipe schematic from manhole C 0563 to C 0562
MH: C 0563MH: C 0562downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05630.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start12 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start12.4 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start19.7 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start40.8 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish53.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start85.7 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start85.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish86 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start220 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292.9 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish360.2 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start376.8 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES454.2 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish457 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish457 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish457 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish458.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish458.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish459.9 ft. AMH - Downstream Manhole, Survey Ends - C 0562

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    19.7 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    53.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    85.7 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    360.2 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    376.8 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
0MWM
85.7FS
53.2CL
457CM
0MWL
4.5DAGS
292.9FS
454.2FS
457SSS
376.8FM
459.9AMHC 0562
86FS
458.3DSC
2SSS
220FS
85.7CL
0.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
19.7FS
360.2FS
0AMHC 0563
12CL
2CM
40.8FS
457CL
458.3DAGS
12.4DSC

Properties (6)

additional_info
SC398411
custom_field_two
2
customer
LACSD
datetime
2019-11-21T01:03:04-08:00
documentation
PROPIPE
is_lateral_inspection
false