Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2019, 08:48 AM
  • 22 0534A_22 0534 _08302019_020507.mp4

Date
08/30/2019
W/O
787621
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00791
PipeID
P16876
Time
1:48 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6799
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_787621_TV22102_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0534A
Downstream MH
22 0534
Dir. of Survey
Downstream
Length Surveyed
261.1 ft.
Total Length
261.1 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
153
O&M Index
2
O&M Quick
2I11
O&M Rating
103
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole 22 0534A to 22 0534
MH: 22 0534AMH: 22 0534downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. VC - Vermin Cockroach, within 8 inches of joint: YES0 ft. AMH - Upstream Manhole, Survey Begins - 22 0534A0 ft. MWM - Water Mark, 35 %of cross sectional area1.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start1.9 ft. MGO - General Observation - MAGNEZIUM H.O COATING THROUGHOUT42 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"45.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"86.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"90.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"143.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"195.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"199.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"244.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS INSIDE248.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"258.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish258.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0534

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAGNEZIUM H.O COATING THROUGHOUT

    1.9 ft. - General Observation - MAGNEZIUM H.O COATING THROUGHOUT

Observations (21)

DistanceCodeObservation
42TFC
0MWL
147.3TFC
1.9SAP
258.6DAGS
258.6SAP
199.8TFC
244.1TFCDEBRIS INSIDE
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
195.5TFC
248.3TFC
261.1AMH22 0534
1.9DAGS
86.4TFC
143.2TFC
0VC
0AMH22 0534A
1.9MGOMAGNEZIUM H.O COATING THROUGHOUT
45.9TFC
0MWM
90.6TFC

Properties (6)

additional_info
SC378556
custom_field_two
3
customer
LACSD
datetime
2019-08-30T01:48:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false