Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2019, 09:05 AM
  • 22 0534_22 0568 _08302019_021811.mp4

Date
08/30/2019
W/O
787621
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00791
PipeID
P16875
Time
2:05 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6799
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_787621_TV22102_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0534
Downstream MH
22 0568
Dir. of Survey
Downstream
Length Surveyed
267.3 ft.
Total Length
267.3 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2I11
O&M Rating
105
Overall Index
2
Overall Quick
Overall Rating
261
Pipe schematic from manhole 22 0534 to 22 0568
MH: 22 0534MH: 22 0568downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05340 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. VC - Vermin Cockroach2.7 ft. MGO - General Observation - MAGNEZIUM H.O COATING THROUGHOUT2.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start35.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"39.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"84.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"88.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"116.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"136.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"185.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS INSIDE189.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS INSIDE233.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"238 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"263.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish263.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK267.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0568

Observation photos (3)

  • General Observation - MAGNEZIUM H.O COATING THROUGHOUT

    2.7 ft. - General Observation - MAGNEZIUM H.O COATING THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MWL
39.4TFA
136.5TFC
0AMH22 0534
0MWM
189.8TFCDEBRIS INSIDE
238TFC
84.7TFC
185.3TFCDEBRIS INSIDE
233.5TFC
88.4TFC
2.7MGOMAGNEZIUM H.O COATING THROUGHOUT
2.7SAP
263.6DAGS
116.6TFC
2.7DAGS
263.6SAP
35.2TFC
0VC
266.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
267.3AMH22 0568

Properties (6)

additional_info
SC378556
custom_field_two
3
customer
LACSD
datetime
2019-08-30T02:05:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false