Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2019, 09:20 AM
  • 22 0533_22 0532 _08302019_023651.mp4

Date
08/30/2019
W/O
787621
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00791
PipeID
P16873
Time
2:20 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6799
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_787621_TV22102_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0533
Downstream MH
22 0532
Dir. of Survey
Downstream
Length Surveyed
368.1 ft.
Total Length
368.1 ft.
Structural Index
3
Structural Quick
3M21
Structural Rating
218
O&M Index
2
O&M Quick
2M11
O&M Rating
145
Overall Index
2
Overall Quick
Overall Rating
363
Pipe schematic from manhole 22 0533 to 22 0532
MH: 22 0533MH: 22 0532downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05330 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 40 %of cross sectional area1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.2 ft. MGO - General Observation - MAGNEZIUM H.O COATING THROUGHOUT3.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"80.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"120.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"157 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"234 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"270.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS INSIDE274.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"339.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"365.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish365.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish368.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK368.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0532

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAGNEZIUM H.O COATING THROUGHOUT

    3.2 ft. - General Observation - MAGNEZIUM H.O COATING THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
368.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
365.6SAP
270.3TFCDEBRIS INSIDE
1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL
368.1AMH22 0532
120.6TF
47.8TF
0AMH22 0533
157TFC
339.2TF
0VC
3.2MGOMAGNEZIUM H.O COATING THROUGHOUT
365.6DAGS
3.1DAGS
274.4TFA
80.2TFC
3.2SAP
234TFC
0MWM

Properties (6)

additional_info
SC378556
custom_field_two
3
customer
LACSD
datetime
2019-08-30T02:20:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false