Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2019, 10:18 AM
  • Section#3_22 0752_22 0751__1272019__I0285.mp4

Date
12/07/2019
W/O
0798221
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00821
PipeID
P17109
Time
2:18 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
I0285
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20191207MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0752
Downstream MH
22 0751
Dir. of Survey
Downstream
Length Surveyed
354.8 ft.
Total Length
354.8 ft.
Structural Index
4
Structural Quick
4N00
Structural Rating
296
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
300
Pipe schematic from manhole 22 0752 to 22 0751
MH: 22 0752MH: 22 0751downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 70% START5.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE19.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG49.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB94.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG95.6 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT102.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB151.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB158.4 ft. MWM - Water Mark, 30 %of cross sectional area175.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG205 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 2" - STUB258.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB307.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB338.3 ft. IR - Infiltration Runner, from 04 to 05 o'clock, within 8 inches of joint: YES351.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE354.3 ft. MGO - General Observation - 70% MAG COAT FINISH354.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG354.8 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observation photos (7)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 70% START

    2 ft. - General Observation - MAG COAT 70% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    19.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    94.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    95.6 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    175.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Infiltration Runner, from 04 to 05 o'clock, within 8 inches of joint: YES

    338.3 ft. - Infiltration Runner, from 04 to 05 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
354.8AMH3:55AM
351.5TFAACTIVE
354.3MGO70% MAG COAT FINISH
0MWL
2SAMSEVERE AGG
158.4MWM
95.6SAMSEVERE AGG UNDER MAG COAT
354.3SAMSEVERE AGG
338.3IR
0MWM
49.8TFCSTUB
307.2TFCSTUB
175.9SAMSEVERE AGG
151.7TFCSTUB
19.9SAMSEVERE AGG
102.8TFCSTUB
2MGOMAG COAT 70% START
0AMH2:20AM
258.8TFCSTUB
5.2TBACTIVE
205TFCSTUB
94.7SAMSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
4
customer
LACSD
datetime
2019-12-07T02:18:02-08:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false