- Date
- 12/07/2019
- W/O
- 0798221
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00821
- PipeID
- P17110
- Time
- 1:30 AM
- Certificate
- 1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- I0285
- Sewer Name
- 22 PUDDINGSTONE TRUNK, SECTS 1&2
- City
- SAN DIMAS
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 23
- Purpose
- Capital Improvement Program Assesment
- Project
- 20191207MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 22 0753
- Downstream MH
- 22 0752
- Dir. of Survey
- Downstream
- Length Surveyed
- 356.8 ft.
- Total Length
- 356.8 ft.
- Structural Index
- 4
- Structural Quick
- 4N21
- Structural Rating
- 294
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 295
Pipe schematic from manhole 22 0753 to 22 0752 Observation photos (5)

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - General Observation - 70% MAG COAT START

41.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

187.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

354.7 ft. - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT