Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2019, 08:45 AM
  • Section#1_22 0754_22 0753__1272019__I0285.mp4

Date
12/07/2019
W/O
0798221
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00821
PipeID
P17111
Time
12:45 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
I0285
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20191207MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0754
Downstream MH
22 0753
Dir. of Survey
Downstream
Length Surveyed
274.6 ft.
Total Length
274.6 ft.
Structural Index
4
Structural Quick
4J00
Structural Rating
224
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
224
Pipe schematic from manhole 22 0754 to 22 0753
MH: 22 0754MH: 22 0753downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG OAT 50% START2.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG7.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG17.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB58.9 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT71.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN119.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB173.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN222.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB267.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB274.1 ft. MGO - General Observation - MAG COAT 60% FINISH274.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG274.6 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (4)

  • General Observation - MAG OAT 50% START

    2 ft. - General Observation - MAG OAT 50% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2.2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    7.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    58.9 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

Observations (16)

DistanceCodeObservation
274.1MGOMAG COAT 60% FINISH
17.7TFCSTUB
274.1SAMSEVERE AGG
2MGOMAG OAT 50% START
7.8SAMSEVERE AGG
0MWL
58.9SAMSEVERE AGG UNDER MAG COAT
274.6AMH1:10AM
71.2TFOPEN
0AMH12:50AM
222.4TFCSTUB
0MWM
267.8TFCSTUB
173.7TFOPEN
2.2SAMSEVERE AGG
119.9TFCSTUB

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2019-12-07T00:45:00-08:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false