Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2019, 12:30 PM
  • Section#5_22 0624_22 0623__1232019__I0277.mp4

Date
12/03/2019
W/O
0806003
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00827
PipeID
P16972
Time
4:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0277
Sewer Name
22 SUNFLOWER TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20191203MDM_SUNFLOWER_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0624
Downstream MH
22 0623
Dir. of Survey
Downstream
Length Surveyed
105.8 ft.
Total Length
105.8 ft.
Structural Index
3
Structural Quick
4C2C
Structural Rating
126
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
126
Pipe schematic from manhole 22 0624 to 22 0623
MH: 22 0624MH: 22 0623downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 STUB2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE- SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2.1 ft. MGO - General Observation - 15" NRCP56.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE105.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG105.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED SPORATIC105.3 ft. MGO - General Observation - MH CONN 9:00 ACTIVE105.8 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE- SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE- SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 15" NRCP

    2.1 ft. - General Observation - 15" NRCP

Observations (13)

DistanceCodeObservation
105.3SAMSEVERE AGG
2.1MGO15" NRCP
2SSSBLISTERING PEELING CONCRETE- SEVERE AGG ATTACHED
105.8AMH4:50AM
0MWL
2SAMSEVERE AGG
0AMH4:35AM
0MGOMH CONN 3:00 ACTIVE
105.3SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED SPORATIC
0MWM
0MGOMH CONN 9:00 STUB
56.9TFAACTIVE
105.3MGOMH CONN 9:00 ACTIVE

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2019-12-03T04:30:07-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false