- Date
- 12/03/2019
- W/O
- 0806003
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00827
- PipeID
- P16973
- Time
- 3:49 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0277
- Sewer Name
- 22 SUNFLOWER TRUNK
- City
- COVINA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 21
- Purpose
- Capital Improvement Program Assesment
- Project
- 20191203MDM_SUNFLOWER_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 22 0625
- Downstream MH
- 22 0624
- Dir. of Survey
- Downstream
- Length Surveyed
- 226.8 ft.
- Total Length
- 226.8 ft.
- Structural Index
- 3
- Structural Quick
- 4H2H
- Structural Rating
- 272
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 272
Pipe schematic from manhole 22 0625 to 22 0624 Observation photos (4)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2.5 ft. - General Observation - 15" NRCP

37.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED