Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2019, 12:19 PM
  • Section#3_02 1657_02 1656__1262019__10283.mp4

Date
12/06/2019
W/O
0798195
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00289
PipeID
P18812
Time
4:19 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
10283
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
LAS ANGLES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20191206MDM_MONTERY_PARK_EXTENSION_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1657
Downstream MH
02 1656
Dir. of Survey
Downstream
Length Surveyed
239.7 ft.
Total Length
239.7 ft.
Structural Index
3
Structural Quick
4I2H
Structural Rating
280
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole 02 1657 to 02 1656
MH: 02 1657MH: 02 1656downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG9 ft. MGP - General Photograph - 15" NRCP21.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG27.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - PEELING CONCRETE SEVERE AGG ATTACHED47.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED52.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED157.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN203.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE231 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN239.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG239.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish - PEELING CONCRETE SEVERE AGG ATTACHED239.7 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (6)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Photograph - 15" NRCP

    9 ft. - General Photograph - 15" NRCP

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    21.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    27.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    47.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    52.4 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (15)

DistanceCodeObservation
0MWM
231TFOPEN
0AMH4:25AM
239.7AMH4:50AM
47.1SSSPEELING CONCRETE SEVERE AGG ATTACHED
239.2SAMSEVERE AGG
203.6TFACTIVE
27.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWL
239.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
157.3TFOPEN
9MGP15" NRCP
52.4SSSPEELING CONCRETE SEVERE AGG ATTACHED
2SAMSEVERE AGG
21.3SAMSEVERE AGG

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2019-12-06T04:19:31-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false