Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2019, 11:26 AM
  • Section#1_02 1658_02 1657A__1262019__10283.mp4

Date
12/06/2019
W/O
0798195
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00289
PipeID
P18814
Time
3:26 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
10283
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
LAS ANGLES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20191206MDM_MONTERY_PARK_EXTENSION_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1658
Downstream MH
02 1657A
Dir. of Survey
Downstream
Length Surveyed
112.9 ft.
Total Length
112.9 ft.
Structural Index
4
Structural Quick
4D00
Structural Rating
92
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
92
Pipe schematic from manhole 02 1658 to 02 1657A
MH: 02 1658MH: 02 1657Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MGO - General Observation - MH CONN 6:00 ACTIVE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8 ft. MGO - General Observation - 15" NRCP13.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG99.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB103.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB112.2 ft. MGO - General Observation - MH CONN 3:00 ACTIVE112.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG112.9 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observation photos (3)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 15" NRCP

    8 ft. - General Observation - 15" NRCP

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    13.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (13)

DistanceCodeObservation
8MGO15" NRCP
112.2MGOMH CONN 3:00 ACTIVE
99.8TFCSTUB
13.8SAMSEVERE AGG
2SAMSEVERE AGG
112.2SAMSEVERE AGG
0MWL
0MGOMH CONN 3:00 ACTIVE
112.9AMH3:55AM
0MGOMH CONN 6:00 ACTIVE
0MWM
103.1TFCSTUB
0AMH3:40AM

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2019-12-06T03:26:39-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false