Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2019, 05:16 AM
  • 16 0379_16 0378A _10312019_212326.mp4

Date
10/31/2019
W/O
793293
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P25897
Time
10:16 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7105
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
16 0379
Downstream MH
16 0378A
Dir. of Survey
Downstream
Length Surveyed
111.7 ft.
Total Length
111.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 16 0379 to 16 0378A
MH: 16 0379MH: 16 0378Adownstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03792 ft. MLC - Lining Change, Cured in place2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start11.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - 40% GREASE-LATERAL/ACTIVE93.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish111.7 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE111.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0378A111.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    111.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
109.3DAGS
0MWM
2MLC
0MWL
111.7MGOCONN @ MH 3 O'CLOCK/ACTIVE
2DAGS
0AMH16 0379
93.9TBA
111.7AMH16 0378A
11.1TBD40% GREASE-LATERAL/ACTIVE
111.7MGOCOCKROACHES IN MANHOLE

Properties (8)

additional_info
SC378736
custom_field_two
4
customer
LACSD
datetime
2019-10-31T22:16:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP
year_laid
39052