Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2019, 07:38 AM
  • 16 0344_16 0343 _10282019_235212.mp4

Date
10/29/2019
W/O
793293
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13395
Time
12:38 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7097
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0344
Downstream MH
16 0343
Dir. of Survey
Downstream
Length Surveyed
299.4 ft.
Total Length
299.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312M
O&M Rating
145
Overall Index
2
Overall Quick
Overall Rating
145
Pipe schematic from manhole 16 0344 to 16 0343
MH: 16 0344MH: 16 0343downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03440 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - SHELF CHIPPED/BROKEN 1 TO 2 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MLC - Lining Change, Cured in place20.6 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. TBD - Tap Break-In Defective, at 09 o'clock, -, , within 8 inches of joint: YES, 4", 6" - 15% GREASE-LATERAL/OPEN221.2 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4", 4" - 70% GREASE-LATERAL/OPEN245.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start299.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE299.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0343299.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • General Observation - SHELF CHIPPED/BROKEN 1 TO 2 O'CLOCK

    0 ft. - General Observation - SHELF CHIPPED/BROKEN 1 TO 2 O'CLOCK

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: YES, Start

    245.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    299.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
245.9DAGS
299.4DAGS
20.6TBA
88.2TBA
299.4MGOCOCKROACHES IN MANHOLE
299.4AMH16 0343
155.8TBD15% GREASE-LATERAL/OPEN
0AMH16 0344
0MWL
2DAGS
0MWM
299.4DAGS
221.2TFD70% GREASE-LATERAL/OPEN
0MGOSHELF CHIPPED/BROKEN 1 TO 2 O'CLOCK
2MLC

Properties (7)

additional_info
SC378728
custom_field_two
4
customer
LACSD
datetime
2019-10-29T00:38:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP