Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2019, 07:30 AM
  • 16 0343_16 0342 _10312019_233858.mp4

Date
11/01/2019
W/O
793293
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13394
Time
12:30 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7105
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
16 0343
Downstream MH
16 0342
Dir. of Survey
Downstream
Length Surveyed
66.4 ft.
Total Length
66.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2B00
O&M Rating
26
Overall Index
2
Overall Quick
Overall Rating
26
Pipe schematic from manhole 16 0343 to 16 0342
MH: 16 0343MH: 16 0342downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03430 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MLC - Lining Change, Cured in place2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start65.4 ft. MGP - General Photograph - DAMAGED TROUGH.65.4 ft. MGO - General Observation - DAMAGED TROUGH.65.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish66.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0342

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph - DAMAGED TROUGH.

    65.4 ft. - General Photograph - DAMAGED TROUGH.

  • General Observation - DAMAGED TROUGH.

    65.4 ft. - General Observation - DAMAGED TROUGH.

Observations (9)

DistanceCodeObservation
65.4MGPDAMAGED TROUGH.
65.4MGODAMAGED TROUGH.
2MLC
0MWM
0AMH16 0343
2DAGS
66.4AMH16 0342
0MWL
65.4DAGS

Properties (7)

additional_info
SC378736
custom_field_two
4
customer
LACSD
datetime
2019-11-01T00:30:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP