Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2019, 10:12 AM
  • 16 0315_16 0314 _11122019_022503.mp4

Date
11/12/2019
W/O
793293
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13366
Time
2:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7117
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0315
Downstream MH
16 0314
Dir. of Survey
Downstream
Length Surveyed
260.2 ft.
Total Length
260.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
102
Pipe schematic from manhole 16 0315 to 16 0314
MH: 16 0315MH: 16 0314downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 6 O'CLOCK/ACTIVE0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03152 ft. MLC - Lining Change, Cured in place2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start113.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN116 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN186.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish258.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE260.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0314

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    258.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
0MWM
0MGOCONN @ MH 6 O'CLOCK/ACTIVE
0MGOCOCKROACHES IN MANHOLE
2MLC
258.6DAGS
258.6MGOCOCKROACHES IN MANHOLE
188.2TFA
186.2TFA
260.2AMH16 0314
113.1TFOPEN
116TBOPEN
2DAGS
0MWL
0AMH16 0315

Properties (7)

additional_info
SC378748
custom_field_two
4
customer
LACSD
datetime
2019-11-12T02:12:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP