Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2019, 08:44 AM
  • 16 0308_16 0307 _11132019_005945.mp4

Date
11/13/2019
W/O
793293
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13359
Time
12:44 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6334
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
20 in.
Width
20 in.
Upstream MH
16 0308
Downstream MH
16 0307
Dir. of Survey
Downstream
Length Surveyed
284.2 ft.
Total Length
284.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3325
O&M Rating
21
Overall Index
2
Overall Quick
Overall Rating
21
Pipe schematic from manhole 16 0308 to 16 0307
MH: 16 0308MH: 16 0307downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03080 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3 ft. MLC - Lining Change, Cured in place32.1 ft. RML - Roots Medium Lateral, at 10 o'clock, 15 %, within 8 inches of joint: NO32.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 90% GREASE/ROOTS-LATERAL35.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 90% ROOTS/LATERAL/ACTIVE35.2 ft. RML - Roots Medium Lateral, at 02 o'clock, 25 %, within 8 inches of joint: NO96 ft. RFL - Roots Fine Lateral, at 10 o'clock96 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 85% ROOTS/ACTIVE98.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 20% GREASE/ACTIVE134.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN137.6 ft. RML - Roots Medium Lateral, at 02 o'clock, 35 %, within 8 inches of joint: NO137.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 85% ROOTS-LATERAL203.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN284 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH284.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0307284.2 ft. MGO - General Observation - CONN @ 3 O'CLOCK/ACTIVE

Observation photos (2)

  • Roots Medium Lateral, at 02 o'clock, 25 %, within 8 inches of joint: NO

    35.2 ft. - Roots Medium Lateral, at 02 o'clock, 25 %, within 8 inches of joint: NO

  • Roots Medium Lateral, at 02 o'clock, 35 %, within 8 inches of joint: NO

    137.6 ft. - Roots Medium Lateral, at 02 o'clock, 35 %, within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
0AMH16 0308
32.2TFD90% GREASE/ROOTS-LATERAL
284.2AMH16 0307
0MWM
35.2TFD90% ROOTS/LATERAL/ACTIVE
32.1RML
284VC@ MH
3MLC
137.6RML
96RFL
284.2MGOCONN @ 3 O'CLOCK/ACTIVE
134.1TFOPEN
35.2RML
137.6TFD85% ROOTS-LATERAL
96TFD85% ROOTS/ACTIVE
203.9TBOPEN
0MWL
98.9TFD20% GREASE/ACTIVE

Properties (7)

additional_info
SC365777
custom_field_two
4
customer
LACSD
datetime
2019-11-13T00:44:34-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP