Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 08:13 AM
  • 16 0298_16 0658 _11142019_001429.mp4

Date
11/14/2019
W/O
793293
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13349
Time
12:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6336
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_793293_TV16031_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0298
Downstream MH
16 0658
Dir. of Survey
Downstream
Length Surveyed
336.5 ft.
Total Length
336.5 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
42
O&M Index
2
O&M Quick
3B2L
O&M Rating
173
Overall Index
2
Overall Quick
Overall Rating
215
Pipe schematic from manhole 16 0298 to 16 0658
MH: 16 0298MH: 16 0658downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 02980 ft. MGO - General Observation - CONN @ 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. MLC - Lining Change, Cured in place188.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 30% GREASE-LATERAL/OPEN220 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Start220 ft. MWL - Water Level, 40 %of cross sectional area225.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4", 6"242 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Finish250 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Start269.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"269.8 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start326 ft. MWL - Water Level, 70 %of cross sectional area334 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish336 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Finish336.5 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish - V336.5 ft. MSA - Survey Abandoned - CAMERA BLOCKED BY DEBRIS

Observation photos (1)

  • Deposits Settled Other,  20 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO, Start

    269.8 ft. - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start

Observations (19)

DistanceCodeObservation
225.5TFA
0MWL
2.4MLC
0AMH16 0298
0MGOCONN @ 3 O'CLOCK/ACTIVE
336.5DSZV
269.8TFA
188.5TFD30% GREASE-LATERAL/OPEN
334DAGS
242MWLS
326MWL
336.5MSACAMERA BLOCKED BY DEBRIS
0MWM
220MWLS
220MWL
336MWLS
250MWLS
2DAGS
269.8DSZ

Properties (7)

additional_info
SC365779
custom_field_two
5
customer
LACSD
datetime
2019-11-14T00:13:54-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP