Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 31, 2019, 05:13 AM
  • F 0063_F 0062 _103019_221425.mp4

Date
10/30/2019
W/O
792836
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10148
Time
10:13 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7081
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_792836_TV02235_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0063
Downstream MH
F 0062
Dir. of Survey
Downstream
Length Surveyed
521 ft.
Total Length
521 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
515
O&M Index
4
O&M Quick
5131
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
523
Pipe schematic from manhole F 0063 to F 0062
MH: F 0063MH: F 0062downstream0 ft. MWL - Water Level, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00630 ft. MWM - Water Mark, 75 %of cross sectional area7.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7.4 ft. MGO - General Observation - MAG COAT THROUGHOUT520.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish520.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish520.7 ft. OBS - Obstacles Built Into Structure, 20 %of cross sectional area, from 09 to 03 o'clock521 ft. AMH - Downstream Manhole, Survey Ends - F 0062

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Built Into Structure, 20 %of cross sectional area, from 09 to 03 o'clock

    520.7 ft. - Obstacles Built Into Structure, 20 %of cross sectional area, from 09 to 03 o'clock

Observations (10)

DistanceCodeObservation
520.7OBS
0MWL
7.4SSS
7.4SAP
0AMHF 0063
521AMHF 0062
7.4MGOMAG COAT THROUGHOUT
520.2SSS
0MWM
520.2SAP

Properties (6)

additional_info
SC378681
custom_field_two
3
customer
LACSD
datetime
2019-10-30T22:13:00-07:00
documentation
PROPIPE
is_lateral_inspection
false